Raritan PX3-5541R-E2 power distribution unit (PDU) 18 AC outlet(s) 2U Black

Raritan PX3-5541R-E2. PDU types: Monitored, Switched, Rack capacity: 2U, Type: Three-phase. AC outlets quantity: 18 AC outlet(s), AC outlet types: C13 coupler, C19 coupler, Power plug: IEC 60320. LED indicators: Status, Cable length: 118.1" (3 m). Monitoring: Power, Voltage. Nominal input voltage: 208 V, Maximum current: 60 A, AC input frequency: 50 - 60 Hz
Manufacturer: Raritan
SKU: 6474331
Manufacturer part number: PX3-5541R-E2
$3,484.00
Monitored and switched rack power distribution unit (2U [horizontal], 17.3kVA, 18 outlets). INPUT: 208v (3-phase DELTA), 60a - IEC 60309 3P+E 9h 60A plug (3P4W); OUTPUT: 6@ C13, 12@ C19 outlets; on 6@ 2-pole, 20a Overcurrent Protectors; FEATURES: Billing-Grade (+/- 1%) Energy Metering [kW, kVA, V, A, Power Factor] - per inlet, per breaker/fuse, per outlet; Remote network monitoring via HTML, JSON-RPC, SSH, Telnet, MODBUS/TCP, and SNMPv3. Onboard embedded processor with minimum 536MHz clock speed, 16MB SPI Flash, and 64MB DDR2 RAM. Cascading upto 16 PDU's using single Ethernet or USB connection. Environmental monitoring [temp/humidity] capable – up to 32 sensors. Individual outlet numbers labeled on chassis. Automated deployment via TFTP, DHCP, SSH(CLI), or USB Flash Drives. WiFi Capable. USB Webcam Capable. iPad/iPhone/Android App. Dual 10/100/1000 Ethernet port. Tri-color status LED per receptacle. Breaker metering and alarming (0V detection). Max Dimensions 440mm x 293mm x 88mm (17.3in x 11.5in x 3.5in). Max Weight 13.5 kg. Maximum ambient temperature 60C at full load.

 

  • Embedded Processor: ARM Cortex A5 536MHZ (Atmel A5D35A), 16MB SPI Flash, 64MB DDR2 RAM
  • Compatible Sensors: Temperature, Humidity, Air Flow, Differential Pressure, Water Leak, and Contact Closure
  • Cascading: Yes, Max 16 PDUs can be daisy chained using a single Ethernet or USB connection
Monitored and switched rack power distribution unit (2U [horizontal], 17.3kVA, 18 outlets). INPUT: 208v (3-phase DELTA), 60a - IEC 60309 3P+E 9h 60A plug (3P4W); OUTPUT: 6@ C13, 12@ C19 outlets; on 6@ 2-pole, 20a Overcurrent Protectors; FEATURES: Billing-Grade (+/- 1%) Energy Metering [kW, kVA, V, A, Power Factor] - per inlet, per breaker/fuse, per outlet; Remote network monitoring via HTML, JSON-RPC, SSH, Telnet, MODBUS/TCP, and SNMPv3. Onboard embedded processor with minimum 536MHz clock speed, 16MB SPI Flash, and 64MB DDR2 RAM. Cascading upto 16 PDU's using single Ethernet or USB connection. Environmental monitoring [temp/humidity] capable – up to 32 sensors. Individual outlet numbers labeled on chassis. Automated deployment via TFTP, DHCP, SSH(CLI), or USB Flash Drives. WiFi Capable. USB Webcam Capable. iPad/iPhone/Android App. Dual 10/100/1000 Ethernet port. Tri-color status LED per receptacle. Breaker metering and alarming (0V detection). Max Dimensions 440mm x 293mm x 88mm (17.3in x 11.5in x 3.5in). Max Weight 13.5 kg. Maximum ambient temperature 60C at full load.

 

  • Embedded Processor: ARM Cortex A5 536MHZ (Atmel A5D35A), 16MB SPI Flash, 64MB DDR2 RAM
  • Compatible Sensors: Temperature, Humidity, Air Flow, Differential Pressure, Water Leak, and Contact Closure
  • Cascading: Yes, Max 16 PDUs can be daisy chained using a single Ethernet or USB connection

Products specifications

Attribute name Attribute value
Load Capacity 17300 VA
Monitoring Power, Voltage
Width 17.3"
Depth 11.5"
Height 3.46"
Weight 29.8 lbs
Mounting Horizontal
Display LCD
Cable Length 118.1"
Type Three-phase
Block 1 output current 12 A
Block 2 output current 16 A
Technical details
Product color Black
Packaging data
Package height 11.2"
Package width 22"
Package depth 21.7"
Package weight 38.6 lbs
Ports & interfaces
AC outlets quantity 18 AC outlet(s)
AC outlet types C13 coupler, C19 coupler
Ethernet LAN (RJ-45) ports 2
USB ports quantity 3
Power plug IEC 60320
Design
PDU types Monitored, Switched
Operational conditions
Operating temperature (T-T) 0 - 60 °C
Operating relative humidity (H-H) 0 - 85 %
Operating altitude 0 - 120000"
Power
Maximum current 60 A
Nominal input voltage 208 V
AC input frequency 50 - 60 Hz
Power protection features Overload
Features
Rack capacity 2U
LED indicators Status
Output voltage 208 - 240 V
Other features
Nominal output voltage 208 V
/* Added for Digitol */ /* End Added for Digitol */